Title of article :
Efficiency of free cooling using latent heat storage integrated into the ventilation system of a low energy building
Author/Authors :
Arkar، نويسنده , , C. and Vidrih، نويسنده , , B. and Medved، نويسنده , , S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
10
From page :
134
To page :
143
Abstract :
This article presents the results of an investigation into the free cooling efficiency in a heavyweight and lightweight low energy building using a mechanical ventilation system with two latent heat thermal energy storages (LHTESs), one for cooling the fresh supply air and the other for cooling the re-circulated indoor air. Both LHTESs contain sphere encapsulated PCM (paraffin RT20). Using a developed and experimentally verified numerical model of the LHTES, the temperature response functions, based on the heat storage size, the air flow rates and the PCMʹs thermal properties, are established in the form of a Fourier series and empirical equations and used in the TRNSYS building thermal response model. Several mechanical ventilation, night cooling and free cooling operation modes were analysed and compared. It was found that the free cooling technique enables a reduction in the size of the mechanical ventilation system, provides more favourable temperatures and therefore enables better thermal comfort conditions, and in our studied case also fresh air for the occupants.
Keywords :
Conditionnement dיair , ةconomie dיénergie , Immeuble , Froid naturel , ventilation , Building , Matériau , ENERGY SAVING , changement de phase , Efficacité , air conditioning , Stockage dיénergie , Free cooling , ventilation , Energy Storage , Material , phase change , optimization , efficiency , Optimisation
Journal title :
International Journal of Refrigeration
Serial Year :
2007
Journal title :
International Journal of Refrigeration
Record number :
1341534
Link To Document :
بازگشت