Title of article :
Refrigerant R134a vaporisation heat transfer and pressure drop inside a small brazed plate heat exchanger
Author/Authors :
Longo، نويسنده , , G.A. and Gasparella، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Abstract :
This paper presents the experimental heat transfer coefficients and pressure drop measured during refrigerant R134a vaporisation inside a small brazed plate heat exchanger (BPHE): the effects of heat flux, refrigerant mass flux, saturation temperature and outlet conditions are investigated. The BPHE tested consists of 10 plates, 72 mm in width and 310 mm in length, which present a macro-scale herringbone corrugation with an inclination angle of 65° and corrugation amplitude of 2 mm.
perimental results are reported in terms of refrigerant side heat transfer coefficients and frictional pressure drop. The heat transfer coefficients show great sensitivity both to heat flux and outlet conditions and weak sensitivity to saturation temperature. The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow.
perimental heat transfer coefficients are also compared with two well-known correlations for nucleate pool boiling and a correlation for frictional pressure drop is proposed.
Keywords :
R134a , ةchangeur à plaques , Expérimentation , Transfert de chaleur , Chute de pression , ةvaporation , R134a , Heat Exchanger , Plate exchanger , heat transfer , Pressure drop , Evaporation , Experiment , ةchangeur de chaleur
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration