Title of article :
Modelling of reciprocating and scroll compressors
Author/Authors :
Duprez، نويسنده , , Marie-Eve and Dumont، نويسنده , , Eric and Frère، نويسنده , , Marc، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Abstract :
This paper presents simple and thermodynamically realistic models of two types of compressors widely used in domestic heat pumps (reciprocating and scroll compressors). These models calculate the mass flow rate of refrigerant and the power consumption from the knowledge of operating conditions and parameters. Some of these parameters may be found in the technical datasheets of compressors whereas others are determined in such a way that the calculated mass flow rate and electrical power match those given in these datasheets.
o models have been tested on five reciprocating compressors and five scroll compressors. This study has been limited to compressors with a maximum electrical power of 10 kW and for the following operating conditions: evaporating temperatures ranging from −20 to 15 °C and condensing temperatures ranging from 15 to 60 °C.
erage discrepancies on mass flow rate and power for reciprocating compressors are 1.10 and 1.69% (for different refrigerants: R134a, R404A, R22, R12 and R407C). For scroll compressors, the average discrepancies on mass flow rate and power are 2.42 and 1.04% (for different refrigerants: R134a, R404A, R407C and R22).
Keywords :
R407C , Réfrigération , Modélisation , Refrigeration , R134a , compresseur à spirale , Performance , air conditioning , R404A , Performance , R407C , Modelling , R22 , Reciprocating piston , Scroll compressor , R134a , R404A , R22 , Compresseur à piston , Conditionnement d’air
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration