Title of article :
Liquid side heat transfer and pressure drop in finned-tube cooling-coils operated with secondary refrigerants
Author/Authors :
Haglund Stignor، نويسنده , , Caroline and Sundén، نويسنده , , Bengt and Fahlén، نويسنده , , Per، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
12
From page :
1278
To page :
1289
Abstract :
In this study full-scale experiments with two different conventional cooling-coils aimed for display cabinets were performed. Heat transfer and pressure drop on the liquid side for three different single phase secondary refrigerants were studied and compared to predictions by existing correlations. Predominantly, the laminar flow regime was studied. The results show that when predicting the heat transfer performance on the liquid side of a cooling-coil the Gnielinski correlation for thermally developing flow and uniform wall temperature boundary conditions (T) leads to good agreement for 0.0014 < x∗ < 0.017 if 50 < Re < 1700, assuming a new entrance length is formed after each U-bend. In addition, these entrance lengths must also be accounted for, when predicting the pressure drop on the liquid side of the cooling-coil. The uncertainty of measurement can be a problem in this type of investigations and this has been taken into consideration when analysing the results.
Keywords :
ةchangeur de chaleur , propylene glycol , Secondary refrigerant , Laminar flow , Expérimentation , Meuble de vente , tube aileté , Transfert de chaleur , Display cabinet , Frigoporteur , heat transfer , finned tube , ةcoulement laminaire , Experiment , Heat Exchanger , Propylène glycol , Pressure drop , Réfrigération , Refrigeration , Chute de pression
Journal title :
International Journal of Refrigeration
Serial Year :
2007