Title of article :
Design of a steady-state detector for fault detection and diagnosis of a residential air conditioner
Author/Authors :
Kim، نويسنده , , Minsung and Yoon، نويسنده , , Seok Ho and Domanski، نويسنده , , Piotr A. and Vance Payne، نويسنده , , W.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
10
From page :
790
To page :
799
Abstract :
This paper presents a general methodology for developing a steady-state detector for a vapor compression system based on a moving window and using standard deviations of seven measurements selected as features. The feature thresholds and optimized moving window size were based upon steady-state no-fault tests and startup transient tests. The study showed that evaporator superheat and condenser subcooling were sufficient for determining the onset of steady-state during the startup transient. However, they misidentified steady-state during indoor temperature change tests where evaporator saturation temperature and air temperature change across the evaporator were needed for proper steady-state identification. Hence, the paper recommends including all fault detection and diagnosis (FDD) features in the steady-state detector to ensure the robustness of the detector because different features may play key roles with different transients.
Keywords :
Fault , Steady state , Conditionneur d’air , Système à compression , Immeuble d’habitation , Procédé , Détection , Anomalie , Régime stable , Air conditioner , Residential building , Compression system , Process , detection
Journal title :
International Journal of Refrigeration
Serial Year :
2008
Journal title :
International Journal of Refrigeration
Record number :
1341783
Link To Document :
بازگشت