• Title of article

    Theoretical analysis of a vapour compression refrigeration system with R502, R404A and R507A

  • Author/Authors

    Arora، نويسنده , , Akhilesh and Kaushik، نويسنده , , S.C.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2008
  • Pages
    8
  • From page
    998
  • To page
    1005
  • Abstract
    This paper presents a detailed exergy analysis of an actual vapour compression refrigeration (VCR) cycle. A computational model has been developed for computing coefficient of performance (COP), exergy destruction, exergetic efficiency and efficiency defects for R502, R404A and R507A. The present investigation has been done for evaporator and condenser temperatures in the range of −50 °C to 0 °C and 40 °C to 55 °C, respectively. The results indicate that R507A is a better substitute to R502 than R404A. The efficiency defect in condenser is highest, and lowest in liquid vapour heat exchanger for the refrigerants considered.
  • Keywords
    Système à compression , Modélisation , COP , R502 , Refrigeration system , R404A , Compression system , R507A , Modelling , COP , Exergy , efficiency , R502 , R404A , R507A , Système frigorifique , Efficacité , exergie
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2008
  • Journal title
    International Journal of Refrigeration
  • Record number