Title of article
Experimental investigation of a liquid-flooded Ericsson cycle cooler
Author/Authors
Hugenroth، نويسنده , , Jason and Braun، نويسنده , , James and Groll، نويسنده , , Eckhard and King، نويسنده , , Galen، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
12
From page
1241
To page
1252
Abstract
An experimental test program was conducted on a novel Ericsson cycle heat pump. The concept uses liquid flooding of the compressor and expander to approach isothermal compression and expansion processes. Open drive automotive scrolls were used in the experimental system. Numerous experiments were run at various conditions using nitrogen as the refrigerant and alkyl-benzene oil as the flooding liquid. Cooling capacities of over 670 W and volumetric cooling capacities of more than 110 kJ/m3 were measured. Second law efficiencies of approximately 3% were achieved. Similar to other gas cycles, the cycle performance is very sensitive to the adiabatic efficiencies of the rotating equipment and the performance of the off-the-shelf equipment was not sufficient to achieve high cycle efficiency. In addition, large pressure drops occurred in the system due to the instrumentation used and the long and arduous flow paths. The scroll compressor and expander were found to perform well considering that they were not designed for the operating conditions encountered.
Keywords
Experiment , GAS , EXPANSION , Compression , Pompe à chaleur , Ericsson , Cycle thermodynamique , Ericsson , Expérimentation , Gaz , Thermodynamic Cycle , Détente , Air , Compression , Heat pump , Air
Journal title
International Journal of Refrigeration
Serial Year
2008
Journal title
International Journal of Refrigeration