• Title of article

    Experimental study on a two-stage rotary desiccant cooling system

  • Author/Authors

    Ge، نويسنده , , T.S. and Li، نويسنده , , Y. and Wang، نويسنده , , R.Z. and Dai، نويسنده , , Y.J.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    11
  • From page
    498
  • To page
    508
  • Abstract
    The objectives of this study were to evaluate the performance of a novel two-stage rotary desiccant cooling (TSRDC) system and to obtain useful data and experiences for practical application. Newly developed compound desiccant (silica gel–haloids) was adopted in the system. An experimental set-up was built and used to test the system performance under three typical environmental conditions. System performances were evaluated in terms of moisture removal D and thermal coefficient of performance COPth. It has found that the required regeneration temperature of TSRDC system is low and COPth of the system is high. Regeneration temperatures from 65 °C to 80 °C, 65 °C to 75 °C and 80 °C to 90 °C were recommended for each environmental condition. In addition, the effects of some important operating parameters, such as inlet temperature and humidity ratio of process and regeneration air, on system performance were also investigated in this study.
  • Keywords
    Conditionnement dיair , Two-stage system , Desiccant system , Desiccant wheel , Roue déshydratante , Performance , Experiment , Performance , Système biétagé , air conditioning , Système à déshydratant , Expérimentation
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2009
  • Journal title
    International Journal of Refrigeration
  • Record number