Title of article :
Numerical simulation of counter-flow wet-cooling towers
Author/Authors :
Heidarinejad، نويسنده , , Ghassem and Karami، نويسنده , , Maryam and Delfani، نويسنده , , Shahram، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
Cooling towers are used to cool a warm water stream through evaporation of part of the water into an air stream. A cooling tower consists of three zones; namely spray, packing and rain zones. In cooling towers, a significant portion of the total heat rejected may occur in the spray and rain zones. These zones are modeled and solved numerically using a computer code. The developed models of these zones are validated against experimental data. For the case study under consideration, the error in calculation of the tower volume is 1.5% when the spray and rain zones are neglected. This error is reduced to 1.1% and 0.25% as the spray and rain zones are incorporated in the model, respectively. Furthermore, the effect of the Lewis factor on the performance prediction of wet-cooling towers is investigated using Bosnjakovic equation.
Keywords :
comparison , Experiment , Tour de refroidissement , Modélisation , Transfert de chaleur , comparaison , Expérimentation , Cooling Tower , Modelling , heat transfer , Mass transfer , Transfert de masse
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration