Effects of biofouling on air-side heat transfer and pressure drop for finned tube heat exchangers
Author/Authors :
Pu، نويسنده , , Hui and Ding، نويسنده , , Guoliang and Ma، نويسنده , , Xiao-kui and Hu، نويسنده , , Hai-tao and Gao، نويسنده , , Yi-feng، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
Experimental investigations on the effects of biofouling on air-side heat transfer and pressure drop for three biofouled finned tube heat exchangers and one clean finned tube heat exchanger were performed. Artificial accelerated method of microorganism growth on the fin surface was used for simulating the biofouled finned tube heat exchangers. Experimental results indicate that the effects of biofouling on the air-side heat transfer coefficient decreases 7.2% at 2.0 m/s when the biofouled area ratio is 10%, while it decreases 15.9% at 2.0 m/s when the biofouled area ratio is 60%, and biofouling causes a 21.8% ∼ 41.3% increase in pressure drop when the air velocity is between 0.5 and 2.0 m/s. The increase of inlet air velocity is helpful to improve the long-term performance of finned tube heat exchanger. Biofouling makes the hydrophilic coating failure, and the condensation water easily converges on the fin surface where biofouling grows.
Keywords :
Tube alietté , Expérimentation , Chute de pression , Transfert de chaleur , Encrassement , Micro-organisme , Heat Exchanger , Experiment , finned tube , heat transfer , Pressure drop , FOULING , Micro-organism , ةchangeur de chaleur