Title of article :
Numerical assessment of steam ejector efficiencies using CFD
Author/Authors :
Varga، نويسنده , , Szabolcs and Oliveira، نويسنده , , Armando C. and Diaconu، نويسنده , , Bogdan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
Ejector efficiencies for the primary nozzle, suction, mixing and diffuser were determined for the first time, according to their definitions, using an axi-symmetric CFD model. Water was considered as working fluid and the operating conditions were selected in a range that would be suitable for an air-conditioner powered by solar thermal energy. Ejector performance was estimated for different nozzle throat to constant section area ratios. The results indicated the existence of an optimal ratio, depending on operating conditions. Ejector efficiencies were calculated for different operating conditions. It was found that while nozzle efficiency can be considered as constant, the efficiencies related to the suction, mixing and diffuser sections of the ejector depend on operating conditions.
Keywords :
Système frigorifique , système à éjecteur , SIMULATION , Géométrie , Dynamique numérique des fluides , Calcul , Refrigeration system , Performance , Ejector system , Rendement , SIMULATION , Geometry , Ejector , Computational fluid dynamics , CALCULATION , Performance , efficiency , ةjecteur
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration