Title of article :
Improved methodologies for simulating unitary air conditioners at off-design conditions
Author/Authors :
Shen، نويسنده , , Bo and Braun، نويسنده , , James E. and Groll، نويسنده , , Eckhard A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Pages :
13
From page :
1837
To page :
1849
Abstract :
Models for unitary air conditioners and heat pumps typically have difficulties in providing accurate predictions for the following situations: 1) charge modeling over a large range of charge levels, 2) two-phase refrigerant entering fixed-orifice expansion devices, 3) two-phase refrigerant entering compressors, and 4) non-uniform refrigerant mass flow allocation among evaporator circuits at low indoor air flow rates. This paper gives descriptions and assessments of improved modeling methodologies for all four issues. The study utilizes data obtained from extensive testing at a wide range of operating conditions for two R-410A units and one R-407C unit.
Keywords :
Simulation , Operation , Variation , Refrigerant charge , flow rate , Conditionnement dיair , Conditionneur dיair , Modélisation , Fonctionnement , Charge en frigorigène , Variation , débit , air conditioning , Modelling , Simulation , Air conditioner
Journal title :
International Journal of Refrigeration
Serial Year :
2009
Journal title :
International Journal of Refrigeration
Record number :
1342407
Link To Document :
بازگشت