Title of article
Modeling of scroll compressors – Improvements
Author/Authors
Duprez، نويسنده , , Marie-Eve and Dumont، نويسنده , , Eric and Frère، نويسنده , , Marc، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2010
Pages
8
From page
721
To page
728
Abstract
This paper presents an improvement of the scroll compressors model previously published by Duprez et al. (2007). This improved model allows the calculation of refrigerant mass flow rate, power consumption and heat flow rate that would be released at the condenser of a heat pump equipped with the compressor, from the knowledge of operating conditions and parameters. Both basic and improved models have been tested on scroll compressors using different refrigerants. This study has been limited to compressors with a maximum electrical power of 14 kW and for evaporation temperatures ranging from −40 to 15 °C and condensation temperatures from 10 to 75 °C. The average discrepancies on mass flow rate, power consumption and heat flow rate are respectively 0.50%, 0.93% and 3.49%. Using a global parameter determination (based on several refrigerants data), this model can predict the behavior of a compressor with another fluid for which no manufacturer data are available.
Keywords
Modelling , Flow , Energy consumption , heat transfer , Synthèse , Modélisation , Amélioration , consommation dיénergie , débit , Screw compressor , Pompe à chaleur , Heat pump , Review , Transfert de chaleur , Improvement , compresseur à spirale
Journal title
International Journal of Refrigeration
Serial Year
2010
Journal title
International Journal of Refrigeration
Record number
1342542