• Title of article

    Optimisation of a desiccant cooling system design with indirect evaporative cooler

  • Author/Authors

    Goldsworthy، نويسنده , , M. and White، نويسنده , , S.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2011
  • Pages
    11
  • From page
    148
  • To page
    158
  • Abstract
    Solar desiccant-based air-conditioning has the potential to significantly reduce cost and/or greenhouse gas emissions associated with cooling of buildings. Parasitic energy consumption for the operation of supply fans has been identified as a major hindrance to achieving these savings. The cooling performance is governed by the trade-off between supplying larger flow-rates of cool air or lower flow-rates of cold air. The performance of a combined solid desiccant-indirect evaporative cooler system is analysed by solving the heat and mass transfer equations for both components simultaneously. Focus is placed on varying the desiccant wheel supply/regeneration and indirect cooler secondary/primary air-flow ratios. Results show that for an ambient reference condition, and 70 °C regeneration temperature, a supply/regeneration flow ratio of 0.67 and an indirect cooler secondary/primary flow ratio of 0.3 gives the best performance with COPe > 20. The proposed cooling system thus has potential to achieve substantial energy and greenhouse gas emission savings.
  • Keywords
    Systéme ل dèshydratant , Conditionnement dיair , Roue dèshydratante , Air-conditioning , Desiccant system , Performance , Performance , Optimisation , Optimisation , Desiccant wheel
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2011
  • Journal title
    International Journal of Refrigeration
  • Record number