Title of article :
Analytical solution for the simultaneous heat and mass transfer problem in air washers
Author/Authors :
Santos، نويسنده , , J.C. and Medeiros، نويسنده , , J.M. and dos Santos، نويسنده , , J.C. and Gurgel، نويسنده , , J.M. and Marcondes، نويسنده , , F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
9
From page :
353
To page :
361
Abstract :
An analytical solution approach for the simultaneous heat and mass transfer problem in air washers operating as evaporative coolers is presented. A one-dimensional model using the coupled mass and energy balance equations in the air washer is presented. Then, starting from a linear approach for the experimental curve of the air saturation, an analytical solution for the model was derived. The solution showed an excellent agreement with the available results found in the literature. The influence of several important parameters for the cooling process such as temperature and ambient air humidity, air flow rate and feeding water temperature, in the air cooling rate was investigated. The efficacy of the process can be greatly increased by reducing the cooling water temperature and the applied air flow rate. The analytical solution can be easily included into the models used for simulating desiccant air-conditioning systems operating in conjunction with air washers.
Keywords :
air conditioning , Air washer , Evaporative system , CALCULATION , Mass transfer , Laveur dיair , Conditionnement dיair , Système évaporatif , Transfert de chaleur , Calcul , Transfert de masse , heat transfer
Journal title :
International Journal of Refrigeration
Serial Year :
2011
Journal title :
International Journal of Refrigeration
Record number :
1342675
Link To Document :
بازگشت