Title of article
Oil type influence on the optimal charge and performance of a propane chiller
Author/Authors
José-M. and Martيnez-Galvلn، نويسنده , , Israel and Gonzلlvez-Maciل، نويسنده , , José and Corberلn، نويسنده , , José-M. and Royo-Pastor، نويسنده , , Rafael، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
8
From page
1000
To page
1007
Abstract
The paper presents the experimental results of a charge optimization study of a water-to-water chiller with two different oils: Mineral and POE. The employed chiller is a prototype which works with propane as refrigerant and provides for a cooling capacity of approximately 16 kW. A complete charge optimization study was performed for two different oils: mineral ISO-VG 68 and POE ISO-VG 22. The study covered a wide range of variation of condensation temperatures, all around the typical operating conditions for AC applications. The obtained performance and compressor efficiencies are studied and discussed to explain the observed differences due to the oil type. The main conclusions are that the optimal charge is strongly different, depending on the solubility of the refrigerant into the oil, and that the POE oil seems to lead to better unit performance.
Keywords
Refroidisseur dיeau , Système frigorifique , Frigorigène , Propane , Oil , Refrigerating system , Water chiller , Refrigerant , charge , Propane , Huile , charge
Journal title
International Journal of Refrigeration
Serial Year
2011
Journal title
International Journal of Refrigeration
Record number
1343116
Link To Document