Abstract :
The performance of the heat pump can be improved further when running under low temperature conditions when an ejector is used in a heat pump system coupled with economized vapor injection (EVI) scroll compressor. In this paper, the design method of the heat pump system with ejector (EVIe) is presented, and the process for designing the heat pump with ejector has been summarized. The optimal location of the vapor injection inlets is at the place where the vapor can inject into the working chambers when they just be closed. The reasonable value for the entrainment ratio u of the ejector is between 0.1 and 0.2. One prototype heat pump was designed under the condition of the evaporation temperature of −20 °C, and an experimental setup was established to test the prototype. The measured results demonstrated that the heating EER of the heat pump system with ejector could reach about 4% higher than that of the system without ejector when the heating capacity remained nearly constant.
Keywords :
injection , Ejector , Design , Pompe à chaleur , Air-eau , compresseur à spirale , injection , ةjecteur , Conception , Calcul , Heat pump , Air-source , Scroll compressor , CALCULATION