Title of article :
Attempt of integration of a small commercial ammonia-water absorption refrigerator with a solar concentrator: Experience and results
Author/Authors :
Busso، نويسنده , , A. and Franco، نويسنده , , J. and Sogari، نويسنده , , N. and Cلceres، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
16
From page :
1760
To page :
1775
Abstract :
The integration of a small commercial ammonia-water absorption refrigerator with a solar concentrator as heat source was analyzed theoretically and experimentally. Operation parameters of the fridge were determined by parametric fitting experimental data using a thermodynamic model of the cycle leading to a working pressure of 25 bar, weak and strong solution concentrations of 15% and 30% respectively and a COP of ∼0.18. As sold, the fridge can operate with a reduction in the electric power supply of up to 40%. Results showed that the Parabolic Concentrator (PC) used can deliver temperatures above 200 °C for almost 6 h with an average useful power delivery and efficiency of 530 W and 26% respectively. During laboratory test runs it was possible to hold the refrigeration cycle running in a very unstable regime despite the inappropriate heat distribution in the generator unit due to the lower temperature heat source used (220 °C). However, outdoor testing with the sun as energy source proved unsuccessful due to the higher heat losses that occur at the pipes connecting the PC with the fridge.
Keywords :
Ammonia , Absorption System , Solar concentration , Thermodynamic property , Système à absorption , Ammoniac , Froid solaire , Concentration du rayonnement solaire , Propriété thermodynamique , Solar refrigeration
Journal title :
International Journal of Refrigeration
Serial Year :
2011
Journal title :
International Journal of Refrigeration
Record number :
1343755
Link To Document :
بازگشت