• Title of article

    Experimental analysis of frost formation with the presence of an electric field on fin and tube evaporator

  • Author/Authors

    Joppolo، نويسنده , , Cesare Maria and Molinaroli، نويسنده , , Luca and De Antonellis، نويسنده , , Stefano and Merlo، نويسنده , , Umberto، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    7
  • From page
    468
  • To page
    474
  • Abstract
    This paper deals with an experimental study carried out to investigate the influence of DC electric fields on the performance of a fin and tube evaporator under frosting conditions. Several experiments are carried out measuring frost mass, air-side pressure drop and cooling capacity for different applied voltage, air velocity and evaporation temperature. Results show that the electric field reduces the frost mass and air-side pressure drop whereas it increases the cooling capacity. Finally, with a superimposed electric field, the overall energy consumption of the refrigerating unit reduces when referred to the same refrigerating effect.
  • Keywords
    givre , Chute de pression , Reduction , Capacity , Evaporator , Experiment , Pressure drop , frost , Réduction , Puissance , Champ électrique , ةvaporateur , Expérience , Electric field
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2012
  • Journal title
    International Journal of Refrigeration
  • Record number