• Title of article

    Dynamic model of an industrial heat pump using water as refrigerant

  • Author/Authors

    Chamoun، نويسنده , , Marwan and Rulliere، نويسنده , , Romuald and Haberschill، نويسنده , , Philippe and Berail، نويسنده , , Jean Francois، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    12
  • From page
    1080
  • To page
    1091
  • Abstract
    In order to improve industrial energy efficiency, the development of a high temperature heat pump using water vapor as refrigerant is investigated. Technical problems restraining the feasibility of this industrial heat pump are surmounted by a specifically designed heat pump and the development of a new twin screw compressor. This article presents the development of a new dynamic model of this twin screw compressor and of the heat pump using flash evaporation. This model takes into account the presence and the purging mechanism (purging reservoir) of the non-condensable gases especially during the start-up procedure. A finite volume (FV) approach is used for the plate heat-exchangers models while a moving boundary (MB) approach between phases is implemented for the purging and the flash evaporation systems models. The models are developed using Modelica as a modeling language without any library involvement and taking into account as many details as possible to closely represent the real system.
  • Keywords
    EAU , Régime transitoire , Modelica , Modélisation , water , high temperature , Modelica , Heat pump , Transient state , MODELING , Pompe à chaleur , Température élevée
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2012
  • Journal title
    International Journal of Refrigeration
  • Record number