• Title of article

    Comparative analysis of low temperature industrial refrigeration systems

  • Author/Authors

    Mumanachit، نويسنده , , P. and Reindl، نويسنده , , D.T. and Nellis، نويسنده , , G.F.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    14
  • From page
    1208
  • To page
    1221
  • Abstract
    This paper compares the energy performance and economics of a direct two-stage ammonia system to an ammonia–carbon dioxide cascade system for low temperature (below −40 °C) applications. Component and system models are developed for both the direct ammonia and the ammonia–carbon dioxide cascade options. These models provide the basis for quantifying the relative operating costs for both systems on annual and life-cycle bases. alysis shows that the ammonia–carbon dioxide cascade system option using a shell-and-tube cascade condenser offers the potential for increased energy efficiency when compared to a direct two-stage ammonia system when operating with evaporating temperatures that are below −46.2 °C. For the cascade system option, the analysis shows that a shell-and-tube cascade heat exchanger with design approach temperature of 5.6 °C provides the optimal balance of system performance with capital cost.
  • Keywords
    optimization , Systeme à cascade , Congelateur industriel , Dioxyde de carbone , Optimisation , Cascade system , Industrial freezer , Ammonia , Carbon dioxide , Ammoniac
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2012
  • Journal title
    International Journal of Refrigeration
  • Record number