Title of article :
Performance optimization of a hybrid ground source heat pump with the parallel configuration of a ground heat exchanger and a supplemental heat rejecter in the cooling mode
Author/Authors :
Park، نويسنده , , Honghee and Lee، نويسنده , , Joo Seoung and Kim، نويسنده , , Wonuk and Kim، نويسنده , , Yongchan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
10
From page :
1537
To page :
1546
Abstract :
A hybrid ground source heat pump (HGSHP) combining a ground flow loop and a supplemental heat rejecter loop in parallel is proposed to overcome the degradation of the ground thermal condition. The objective of this study is to optimize the performance of the HGSHP with the parallel configuration by varying the amount of refrigerant charge, the secondary fluid flow rate of the ground loop, and the secondary fluid flow rate of the supplemental loop. The coefficient of performance (COP) of the HGSHP with the parallel configuration was 21% higher than that of the conventional ground source heat pump (GSHP), and the heat rejection rate of the ground flow loop was 42% lower than that of the GSHP at the entering fluid temperature (EFT) of 40 °C in the ground heat exchanger and the EFT of 28 °C in the supplemental heat exchanger.
Keywords :
Performance , Optimisation , COP , débit , Heat pump , Ground source , optimization , Performance , COP , fFow rate , Pompe à chaleur , Sol-eau
Journal title :
International Journal of Refrigeration
Serial Year :
2012
Journal title :
International Journal of Refrigeration
Record number :
1344872
Link To Document :
بازگشت