Title of article :
Experimental investigation of the COP improvement of a refrigeration cycle by use of an ejector
Author/Authors :
Lucas، نويسنده , , Christian and Koehler، نويسنده , , Juergen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
9
From page :
1595
To page :
1603
Abstract :
In the present study an experimental comparison between the standard CO2 expansion valve refrigeration cycle and the ejector refrigeration cycle is presented. High pressure variations for different evaporation pressures and gas cooler outlet temperatures were performed. Additionally, the ejector efficiency, the entrainment ratio, and the pressure recovery by the ejector were investigated at these conditions. Both investigated cycles where realized using the same test rig, thus minimizing comparison errors. Compared to the maximal COP of the expansion valve cycle, COP improvements of the ejector cycle of 17% were reached with ejector efficiencies of up to 22%.
Keywords :
Ejector , Refrigerating system , Experimentation , R744 , COP , Dioxyde de carbone , R744 , ةjecteur , Système frigorifique , Performance , Performance , Expérimentation , COP , Carbon dioxide
Journal title :
International Journal of Refrigeration
Serial Year :
2012
Journal title :
International Journal of Refrigeration
Record number :
1344896
Link To Document :
بازگشت