Title of article
Experimental performance study of a small wall room air conditioner retrofitted with R290 and R1270
Author/Authors
Wu، نويسنده , , J.H. and Yang، نويسنده , , L.D. and Hou، نويسنده , , J.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2012
Pages
9
From page
1860
To page
1868
Abstract
An original R22 wall room air conditioner with a cooling capacity of 2.4 kW and energy efficiency ratio (EER) of 3.2 is retrofitted with a compressor of a 20% larger displacement to charge R290 and R1270 for performance experiments. The results show that for R1270, only adopting a same kind mineral lubricant of higher viscosity would supply 2.4% higher cooling capacity and 0.8% higher EER than those of the original R22 system under normal condition, and for R290, adopting the larger displacement compressor simultaneously would also obtain better performance. Alternative systems all have higher increase rate and greater increment in both cooling capacity and EER than the original R22 system when outdoor temperature decreases. The R1270 system has great increase in cooling capacity and negligible decrease in EER. Refrigerant charge distribution is also investigated and it indicates that the charge within both heat exchangers and compressor ought to be reduced.
Keywords
Room air conditioner , R1270 , R1270 , Conditionneur dיair individuel , Distribution de la charge , Charge distribution , Performance , R290 , Performance , R290
Journal title
International Journal of Refrigeration
Serial Year
2012
Journal title
International Journal of Refrigeration
Record number
1344994