Title of article :
Experimental study on an adsorption chiller employing lithium chloride in silica gel and methanol
Author/Authors :
Gong، نويسنده , , L.X. and Wang، نويسنده , , R.Z. and Xia، نويسنده , , Z.Z. and Lu، نويسنده , , Z.S.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
8
From page :
1950
To page :
1957
Abstract :
A novel composite adsorbent – methanol adsorption chiller was proposed and manufactured. It was filled by the adsorbent composed by Lithium Chloride and silica gel. Methanol was used as adsorbate and refrigerant. Experiment results showed that compared with silica gel-water chiller, SCP (specific cooling power) and COP (coefficient of performance) of this novel chiller were improved by 16.3% and 24.2% separately when the temperatures of hot water inlet, cooling water inlet and chilled water outlet were 85 °C, 30 °C and 15 °C.
Keywords :
Méthanol , Adsorption system , Performance , lithium chloride , Silica gel , Système à adsorption , Methanol , Chlorure de lithium , Gel de silice , Performance
Journal title :
International Journal of Refrigeration
Serial Year :
2012
Journal title :
International Journal of Refrigeration
Record number :
1345003
Link To Document :
بازگشت