Abstract :
The performance of desiccant wheel (DW)-assisted separate sensible and latent cooling (SSLC) air-conditioning systems has been greatly improved by the application of divided heat exchangers, resulting in 7% and 46% increases in COP for R410A and CO2 systems, respectively. The paper simulated new performance-enhancing options that include evaporative cooling, a sensible wheel (SW) and an enthalpy wheel (EW) to the SSLC systems. The application of evaporative cooling to the SSLC system further improves the system COP by 7% and 14% respectively. By applying an EW to the SSLC systems, the COP is improved by 39% and 40% respectively. The DW-assisted SSLC technology also can be adopted for the dedicated outdoor system (DOS). It is concluded that only the EW is effective for enhancing the DW-assisted SSLC DOS systems because it lowers not only the cooling requirement of the vapor compression cycle, but also the heat requirement for DW regeneration.
Keywords :
R410A , Refroidissement évaporatif , Sensible cooling , Carbon dioxide , R410A , Evaporative cooling , Heat recovery wheel , Refroidissement à chaleur sensible , Refroidissement à chaleur latente , Latent cooling , Roué déshydratante , Dioxyde de carbone , Roue de récupération de chaleur , Desiccant wheel