Title of article :
Heat transfer during evaporation of R1234ze(E), R32, R410A and a mixture of R1234ze(E) and R32 inside a horizontal smooth tube
Author/Authors :
Anowar Hossain، نويسنده , , Md. and Onaka، نويسنده , , Yoji and Afroz، نويسنده , , Hasan M.M. and Miyara، نويسنده , , Akio، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
13
From page :
465
To page :
477
Abstract :
This experimental study measured and compared the heat transfer coefficients during in-tube evaporation of R1234ze(E), R32, the nearly azeotropic HFC refrigerant blend R410A and a zeotropic mixture R1234ze(E)/R32 (55/45 mass %) inside a water heated double tube heat exchanger. The experiment has been carried out under the conditions of mass flux varying from 150 to 445 kg m−2 s−1, the saturation temperatures are 5 and 10 °C, over the vapor quality range 0.0–1.0. The effect of vapor quality, mass flux and saturation temperature on heat transfer coefficients have been analyzed. It is found that the experimental heat transfer coefficients of R1234ze(E) are lower than R1234ze(E)/R32 (55/45mass%), R410A and R32 by 11%, 56% and 83%, respectively, at about 0.48 vapor quality and 300 kg m−2 s−1 mass velocity. Experimental results have been compared with some well-known correlations.
Keywords :
Coefficient de transfert de chaleur , Two-phase flow , ةvaporation , Heat transfer coefficient , Horizontal tube , Mixture , Evaporation , Mélange , ةcoulement diphasique , Tube horizontal
Journal title :
International Journal of Refrigeration
Serial Year :
2013
Journal title :
International Journal of Refrigeration
Record number :
1345128
Link To Document :
بازگشت