Title of article
Condensation of the low GWP refrigerant HFC1234yf inside a brazed plate heat exchanger
Author/Authors
Longo، نويسنده , , Giovanni A. and Zilio، نويسنده , , Claudio، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
10
From page
612
To page
621
Abstract
This paper presents the heat transfer coefficients and the pressure drop measured during condensation of the new low Global Warming Potential (GWP) refrigerant HFO1234yf inside a brazed plate heat exchanger: the effects of saturation temperature, refrigerant mass flux and vapour super-heating are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature and great sensitivity to refrigerant mass flux. At low refrigerant mass flux (<20 kg m−2 s−1) the heat transfer coefficients are not dependent on mass flux and condensation is controlled by gravity. For higher refrigerant mass flux (>20 kg m−2 s−1) the heat transfer coefficients depend on mass flux and forced convection condensation occurs. The condensation heat transfer coefficients of super-heated vapour are from 8 to 11% higher than those of saturated vapour. HFO1234yf exhibits heat transfer coefficients lower (10–12%) and frictional pressure drop lower (10–20%) than those of HFC134a under the same operating conditions.
Keywords
Condensation , Chute de pression , GWP , surchauffe , Super-heat , Heat transfer coefficient , Coefficient de transfert de chaleur , GWP , Condensation , Pressure drop