Experimental analysis of R1234yf as a drop-in replacement for R134a in a vapor compression system
Author/Authors
Navarro-Esbrي، نويسنده , , J. and Mendoza-Miranda، نويسنده , , J.M. and Mota-Babiloni، نويسنده , , A. and Barragلn-Cervera، نويسنده , , A. and Belman-Flores، نويسنده , , J.M.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
11
From page
870
To page
880
Abstract
This paper presents an experimental analysis of a vapor compression system using R1234yf as a drop-in replacement for R134a. In this work, we compare the energy performance of both refrigerants, R134a and R1234yf, in a monitored vapor compression system under a wide range of working conditions. So, the experimental tests are carried out varying the condensing temperature, the evaporating temperature, the superheating degree, the compressor speed, and the internal heat exchanger use. Comparisons are made taking refrigerant R134a as baseline, and the results show that the cooling capacity obtained with R1234yf in a R134a vapor compression system is about 9% lower than that obtained with R134a in the studied range. Also, when using R1234yf, the system shows values of COP about 19% lower than those obtained using R134a, being the minor difference for higher condensing temperatures. Finally, using an internal heat exchanger these differences in the energy performance are significantly reduced.
Keywords
R1234yf , Vapor compression system , Low GWP , Remplacement immédiat , R1234yf , R134a , Système à compression de vapeur , échangeur de chaleur interne , faible GWP , Drop-in , Internal heat exchanger , R134a
Journal title
International Journal of Refrigeration
Serial Year
2013
Journal title
International Journal of Refrigeration
Record number
1345163
Link To Document