Title of article :
Energy and exergy analysis applied to the evaporative cooling process in air washers
Author/Authors :
Santos، نويسنده , , J.C. and Barros، نويسنده , , G.D.T. and Gurgel، نويسنده , , J.M. and Marcondes، نويسنده , , F.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
8
From page :
1154
To page :
1161
Abstract :
This paper presents a study on the performance of the evaporative cooling process in air washers with the use of mass balances, energy and exergy equations. Usually, the performance of these devices is described in terms of their saturation effectiveness based on energy analysis. This method, however, is inappropriate to identify the main sources of irreversibility within the process. It is also unsuitable to give the optimum conditions for operating the system with a proper use of energy resources. Thus, an exergy analysis was developed to complement the energy analysis of the process. A mathematical model based on mass and energy balances was used to determine the water and air properties in the washer. The influence of the humidity and temperature of the air and water at the inlet, the washer length in the saturation effectiveness, and the second law efficiency was investigated. The results showed that the best condition of the intake air for obtaining thermal comfort does not coincide with the best condition for the thermodynamic performance of the system. The energy and exergy analyses were carried out simultaneously to generate the conditions required for optimum performance with minimal exergy depletion.
Keywords :
Evaporative cooling , Saturation effectiveness , Second law , Refroidissement évaporatif , Laveur dיair , deuxième principe , efficacité de la saturation , Air washer
Journal title :
International Journal of Refrigeration
Serial Year :
2013
Journal title :
International Journal of Refrigeration
Record number :
1345211
Link To Document :
بازگشت