Title of article
Effect of micro-grooves on the two-phase pressure drop of CO2 in a mini-channel tube
Author/Authors
Kim، نويسنده , , Dae-hwan and Jeong، نويسنده , , Siyoung، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
8
From page
2040
To page
2047
Abstract
The pressure drop characteristics of CO2 have been experimentally investigated for a mini-channel tube with and without micro rectangular grooves. The multiple mini-channels have an inner diameter of 0.8 mm and the grooves have a rectangular cross section (0.1 × 0.2 mm). The pressure drop was measured for a saturated liquid phase and two-phase. Using the hydraulic diameter, the pressure drop in the grooved mini-channel can be successfully estimated with the correlations used for smooth channels. Because of a smaller hydraulic diameter, the pressure drop of the grooved channel was found to be about 1.3 times and 1.1–1.45 times greater than that of the smooth channel, for liquid and two-phase, respectively. The experimental results were compared with widely used two-phase pressure drop models. Most of the models showed the mean absolute error of 17–35% for the smooth channel and 13–32% for the grooved channel.
Keywords
Chute de pression , micro-rainures , two-phase , Pressure drop , Micro-grooves , Mini-channel , Carbon dioxide , Diphasique , mini-canal , Dioxyde de carbone