Abstract
This paper deals with the problem of R314a substitution with a natural refrigerant fluid. A comparison is performed between R134a and R744 (CO2). R134a is a hydrofluorocarbon with a large direct warming impact (GWP), whereas the R744 contribution is negligible. A comparative exergetic analysis, carried out with experimental tests, has been presented. This paper compares a commercial R134a refrigeration plant and a prototype R744 system working in a trans-critical cycle. Based on the experimental data an exergetic analysis has been carried out on the overall plant and on each device. The overall exergetic performances of the classical vapour compression plant working with R134a are consistently better than that of R744 (from a minimum of 20 to a maximum of 44%). The performance of the individual components of the plant has been analyzed, in order to pinpoint those contributing most to the decrease in the exergetic performance of R744.
Keywords
CO2 , Transcritical cycle , exergetic analysis , Exergy loss , Dioxyde de carbone , R134a , Perte dיexergie , Cycle transcritique , analyse exergétique , R134a