Title of article :
The substitution of R134a with R744: An exergetic analysis based on experimental data
Author/Authors :
Aprea، نويسنده , , Ciro and Greco، نويسنده , , Adriana and Maiorino، نويسنده , , Angelo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
12
From page :
2148
To page :
2159
Abstract :
This paper deals with the problem of R314a substitution with a natural refrigerant fluid. A comparison is performed between R134a and R744 (CO2). R134a is a hydrofluorocarbon with a large direct warming impact (GWP), whereas the R744 contribution is negligible. A comparative exergetic analysis, carried out with experimental tests, has been presented. This paper compares a commercial R134a refrigeration plant and a prototype R744 system working in a trans-critical cycle. Based on the experimental data an exergetic analysis has been carried out on the overall plant and on each device. The overall exergetic performances of the classical vapour compression plant working with R134a are consistently better than that of R744 (from a minimum of 20 to a maximum of 44%). The performance of the individual components of the plant has been analyzed, in order to pinpoint those contributing most to the decrease in the exergetic performance of R744.
Keywords :
CO2 , Transcritical cycle , exergetic analysis , Exergy loss , Dioxyde de carbone , R134a , Perte dיexergie , Cycle transcritique , analyse exergétique , R134a
Journal title :
International Journal of Refrigeration
Serial Year :
2013
Journal title :
International Journal of Refrigeration
Record number :
1345530
Link To Document :
بازگشت