• Title of article

    Experimental analysis of a new method for overfeeding multiple evaporators in refrigeration systems

  • Author/Authors

    Minetto، نويسنده , , Silvia and Brignoli، نويسنده , , Riccardo and Zilio، نويسنده , , Claudio and Marinetti، نويسنده , , Sergio، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    9
  • From page
    1
  • To page
    9
  • Abstract
    An innovative method for feeding flooded evaporators, arranged in parallel in R744 plants, is presented. In order to promote evaporators overfeeding, an ejector circulates liquid from the low pressure receiver back to the intermediate pressure receiver. Since there is not a need for superheat at the evaporator exit, each evaporator expansion valve can be controlled by a signal representative, either of the evaporator load, or the evaporator performance, such as the air temperature at its inlet or outlet. When compared to dry-expansion evaporator systems, the proposed solution offers energy saving and smooth operating conditions, typical of flooded evaporators, while still maintaining a simple plant lay-out. The concept was experimentally validated: the evaporators were maintained in flooded conditions, while the ejector was able to promote liquid recirculation. Direct comparison with dry-expansion operations was performed. The suggested method is mainly intended for commercial refrigeration plants, where many evaporators are arranged in parallel.
  • Keywords
    Cycle transcritique , Flooded evaporator , CO2 , Thermostatic valve , Ejector , Transcritical cycle , CO2 , Evaporateur noyé , Détendeur thermostatique , Ejecteur
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2014
  • Journal title
    International Journal of Refrigeration
  • Record number

    1345784