Title of article :
Effect of vapor-injection technique on the performance of a cascade heat pump water heater
Author/Authors :
Roh، نويسنده , , Chul Woo and Kim، نويسنده , , Min Soo، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Pages :
10
From page :
168
To page :
177
Abstract :
In this study, we applied a vapor-injection (VI) technique in a cascade heat pump system. The VI was applied to both upper and lower stage cycles. Test results showed that heating and cooling capacities increased by using the VI technique (12% and 6%, respectively); however, the system COP decreased (6.6% at the injection ratio of 16.7%). The cascade system which has a small compression ratio and a cascade condenser, cannot fully utilize the VIʹs advantages to improve the system COP. However, the VI is effective for the system reliability and capacity improvement. We also found that the VI in the upper and lower stage cycles had different effect on overall cycle operating characteristic.
Keywords :
Pompe à chaleur , Chauffe-eau , Injection de vapeur , Cascade , Heat pump , R404A , Vapor injection , Water heater , Cascade , R404A
Journal title :
International Journal of Refrigeration
Serial Year :
2014
Journal title :
International Journal of Refrigeration
Record number :
1345831
Link To Document :
بازگشت