Abstract :
This paper presents the results of an experimental investigation in which the performance of the low-pressure fluids R134a and R1234yf was compared between a two-phase ejector cycle and expansion valve cycles. An alternate two-phase ejector cycle, in which the pressure lift provided by the ejector was utilized in order to provide multiple evaporation temperatures, was constructed and tested. The experimental results show that ejectors designed for low-pressure fluids were able to achieve similar but lower work recovery efficiencies compared to CO2 ejectors. When compared to a two evaporation temperature expansion valve cycle, the ejector cycle showed maximum COP improvements of 12% with R1234yf and 8% with R134a. When compared to a single evaporation temperature expansion valve cycle, the ejector cycle showed maximum COP improvements of 6% with R1234yf and 5% with R134a. The effect of evaporator design on ejector cycle COP improvement was also demonstrated experimentally.
Keywords :
Ejector , Expansion work recovery , Cycle comparison , Coefficient of Performance , Evaporator design , Ejecteur , Comparaison de cycle , Récupération du travail de détente , Coefficient de performance , Conception de lיévaporateur