Title of article :
Performance test of solar-assisted ejector cooling system
Author/Authors :
Huang، نويسنده , , Bin-Juine and Ton، نويسنده , , Wei-Zhe and Wu، نويسنده , , Chen-Chun and Ko، نويسنده , , Hua-Wei and Chang، نويسنده , , Hsien-Shun and Hsu، نويسنده , , Hang-Yuen and Liu، نويسنده , , Jen-Hao and Wu، نويسنده , , Jia-Hung and Yen، نويسنده , , Rue-Her، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2014
Pages :
14
From page :
172
To page :
185
Abstract :
A solar-assisted ejector cooling/heating system (SACH-2k) is built and test result is reported. The solar-driven ejector cooling system (ECS) is connected in series with an inverter-type air conditioner (IAC). Several advanced technologies are developed in SACH-k2, including generator liquid level control in ECS, the ECS evaporator temperature control, and optimal control of fan power in cooling tower of ECS. he field test results, the generator liquid level control performs quite well and keeps stable performance of ejector. The ECS evaporator temperature control also performs satisfactorily to keep ejector performance normally under low or fluctuating solar radiation. The fan power control system cooling tower performs stably and reduces the power consumption dramatically without affecting the ECS performance. The test results show that the overall system COPo including power consumptions of peripheral increases from 2.94–3.3 (IAC alone) to 4.06–4.5 (SACH-k2), about 33–43%. The highest COPo is 4.5.
Keywords :
Ejecteur , Economie dיénergie , Energie solaire , Ejector , ENERGY SAVING , Froid solaire , Solar energy , Solar refrigeration
Journal title :
International Journal of Refrigeration
Serial Year :
2014
Journal title :
International Journal of Refrigeration
Record number :
1345924
Link To Document :
بازگشت