• Title of article

    Experimental evaluation of an ejector as liquid re-circulator in a falling-film water chiller

  • Author/Authors

    Li، نويسنده , , YingLin and Tan، نويسنده , , Laizai and Zhang، نويسنده , , Xiaosong and Du، نويسنده , , Kai، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2014
  • Pages
    8
  • From page
    309
  • To page
    316
  • Abstract
    To experimentally evaluate the performance of an ejector working as a liquid re-circulator in a horizontal-tube falling-film evaporator with R134a, experimental tests are performed using a horizontal-tube falling-film water chiller prototype. Experimental observations on intertube liquid flow pattern of tube bundle validate the feasibility of the liquid re-circulation system using a liquid–liquid ejector. The analysis results show that the influence of the motive flow rate on the entrainment ratio of the ejector is small, and the average entrainment ratio of the ejector is about 2.03. With the increase of the valve opening of the regulating valve, the evaporating capacity of the falling-film water chiller rises 4.8%, from 940.2 kW with the re-circulation ratio of one, to 985.5 kW with the re-circulation ratio of 1.135. The COP of the falling-film water chiller reaches a maximum and then drops down with the increase of the re-circulation ratio, and the optimal re-circulation ratio is 1.135.
  • Keywords
    Entrainment ratio , Film tombant , éjecteur liquide/liquide , Taux dיentraînement , Liquid–liquid ejector , Falling Film , Re-circulation ratio , Taux de re-circulation