Abstract :
This paper presents a method of leak detection in a single pipe where the behaviour of the system frequency response diagram (FRD) is used as an indicator of the pipe integrity. The presence of a leak in a pipe imposes a pattern on the resonance peaks of the FRD that can be used as a clear indication of leakage. Analytical expressions describing the pattern of the resonance peaks are derived. Illustrations of how this pattern can be used to individually locate and size multiple leaks within the system are presented. Practical issues with the technique, such as the procedure for frequency response extraction, the impact of measurement position, noise- and frequency-dependent friction are also discussed.