Title of article
Relay-based critical point estimation of a process with the PID controller in the loop
Author/Authors
?ekara، نويسنده , , Tomislav B. and Matau?ek، نويسنده , , Miroslav R.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2011
Pages
5
From page
1084
To page
1088
Abstract
The proposed procedure is implemented without breaking the loop with the controller in operation, by activating a cascade of band-pass filters in series with a relay in the inner loop and a notch filter in the outer loop. A highly accurate estimate of the critical point of a process G p ( s ) is obtained in the presence of measurement noise and load disturbance. The effectiveness of the proposed procedure is illustrated using a test batch consisting of stable, integrating and unstable processes, including dead-time.
Keywords
critical point , Closed-loop control , relay , Noise and load disturbance
Journal title
Automatica
Serial Year
2011
Journal title
Automatica
Record number
1448329
Link To Document