• Title of article

    Modeling and control of C-UPFC for power system transient studies

  • Author/Authors

    Ajami، نويسنده , , A. and Hosseini، نويسنده , , S.H. and Khanmohammadi، نويسنده , , S. and Gharehpetian، نويسنده , , G.B.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    13
  • From page
    564
  • To page
    576
  • Abstract
    This paper presents the transient model of a new FACTS device, the center node unified power flow controller (C-UPFC), installed at the midpoint of a transmission line. The C-UPFC consists of three voltage source inverters (VSI) with common DC link. One of the converters is connected in parallel at the midpoint of line and the other two converters are connected in series. The simulation results indicate that the C-UPFC is capable of independently controlling the active and reactive power flows at the both ends of line and the magnitude of AC voltage at line mid point. It is shown that by adding a supplementary control system to the shunt inverter control system, it is possible to balance line current too.
  • Keywords
    Power system transient , C-UPFC , FACTS , Converter modeling , UPFC
  • Journal title
    Simulation Modelling Practice and Theory
  • Serial Year
    2006
  • Journal title
    Simulation Modelling Practice and Theory
  • Record number

    1580506