Title of article :
Effect of cold inflow on chimney height of natural draft cooling towers
Author/Authors :
Chu، نويسنده , , Chi-Ming and Rahman، نويسنده , , Md. Mizanur and Kumaresan، نويسنده , , Sivakumar، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
7
From page :
125
To page :
131
Abstract :
Temperature and pressure drop data obtained from an air-cooled heat exchanger model with cross-sectional flow areas of 0.56 m2, 1.00 m2 and 2.25 m2 operating under natural convection are presented that indicate significant cold inflow, resulting in the reduction of effective chimney height. Cold inflows encountered in actual applications where the Froude number is typically 0.2, may not be as severe as described in this paper, which was of the order of 10−6–10−4. Additional tests on smaller scale models appeared to favor the explanation that the occurrence of cold inflow in the air-cooled heat exchanger model was primarily due to the relative ease in either drawing cold air from inlet or from outlet, and to a lesser extent the Froude number of the chimney or the critical velocity estimated by Jörg and Scorerʹs (1967) formula. A CFD study will bring much understanding of the phenomenon for the different situations.
Journal title :
Nuclear Engineering and Design Eslah
Serial Year :
2012
Journal title :
Nuclear Engineering and Design Eslah
Record number :
1592335
Link To Document :
بازگشت