Title of article :
Energy performance of building envelopes in different climate zones in China
Author/Authors :
Yang، نويسنده , , Liu and Lam، نويسنده , , Joseph C. and Tsang، نويسنده , , C.L.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
18
From page :
800
To page :
817
Abstract :
Energy performance of office building envelope designs in the five major climate zones – severe cold, cold, hot summer and cold winter, mild, and hot summer and warm winter – in China was investigated. A major city within each climate zone was selected. These were Harbin, Beijing, Shanghai, Kunming and Hong Kong. Generic building envelopes were developed based on data gathered from building surveys, local energy codes and the ASHRAE Standard. The overall thermal transfer value (OTTV) method and the heating degree-days technique were adopted in the analysis. Cooling and heating requirements due to heat gain/loss through the building envelopes were determined based on the respective OTTV parameters and building load coefficients. Different shape coefficients were also considered. For a typical floor, chiller load due to heat gain through the building envelope varied from 1.0 kW h/m2 in Kunming to 23.5 kW h/m2 in Beijing, and the heating load ranged from 2.7 kW h/m2 in Hong Kong to 124.3 kW h/m2 in Harbin.
Keywords :
Climate zones , Building envelopes , COOLING , CHINA , Heating loads
Journal title :
Applied Energy
Serial Year :
2008