Title of article :
Experimental study of an air-source heat pump for simultaneous heating and cooling – Part 2: Dynamic behaviour and two-phase thermosiphon defrosting technique
Author/Authors :
Byrne، نويسنده , , Paul and Miriel، نويسنده , , Jacques and Lenat، نويسنده , , Yves، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
7
From page :
3072
To page :
3078
Abstract :
This article presents the concepts of an air-source heat pump for simultaneous heating and cooling (HPS) designed for hotels and smaller residential, commercial and office buildings in which simultaneous needs in heating and cooling are frequent. The main advantage of the HPS is to carry out simultaneously space heating and space cooling with the same energy input. Ambient air is used as a balancing source to run a heating or a cooling mode. The second advantage is that, during winter, energy recovered by the subcooling of the refrigerant is stored at first in a water tank and used subsequently as a cold source at the water evaporator to improve the average performance and to carry out defrosting of the air evaporator using a two-phase thermosiphon. Unlike conventional air-source heat pumps, defrosting is carried out without stopping the heat production. A R407C HPS prototype was built and tested. The basic concepts of the HPS are detailed in part1 of this article [1]. Its performance on defined operating conditions corresponds to the data given by the selection software of the compressor manufacturer. In the present part of this article, the operation of the high pressure control system, the transitions between heating, cooling and simultaneous modes and the defrosting sequence are analysed and validated experimentally.
Keywords :
Heat pump , Thermosiphon , COOLING , heating , Defrosting
Journal title :
Applied Energy
Serial Year :
2011
Journal title :
Applied Energy
Record number :
1604764
Link To Document :
بازگشت