Title of article :
Performance analysis of an integrated UFAD and radiant hydronic slab system
Author/Authors :
Raftery، نويسنده , , Paul and Lee، نويسنده , , Kwang Ho and Webster، نويسنده , , Tom and Bauman، نويسنده , , Fred، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2012
Pages :
8
From page :
250
To page :
257
Abstract :
In this paper, an EnergyPlus model was used to simulate the operation of a novel integrated HVAC system. This system combines an underfloor air distribution system with a cooled radiant ceiling slab. A cooling tower supplies water to pre-cool the structural slabs during the night and early morning period. The paper compares the performance of this system to both a typical overhead system and a typical UFAD system in the cooling season for the Sacramento, California climate. When compared to the overhead system, the integrated UFAD/Radiant system shows a 22–23% reduction in total energy consumption during the peak cooling months (June to August) and a 31% reduction in peak hourly electricity demand. When compared to the UFAD system, these reductions are 21–22% and 24% respectively. An investigation of the simulation results showed that the integrated UFAD/Radiant system also improves occupant thermal comfort and reduces thermal decay issues in the underfloor plenum.
Keywords :
Underfloor air distribution , Thermally activated building systems , EnergyPlus , Energy performance , Radiant Cooling , Hydronic slab
Journal title :
Applied Energy
Serial Year :
2012
Journal title :
Applied Energy
Record number :
1605134
Link To Document :
بازگشت