Title of article
Ongoing commissioning of water-cooled electric chillers using benchmarking models
Author/Authors
Monfet، نويسنده , , Danielle and Zmeureanu، نويسنده , , Radu، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2012
Pages
10
From page
99
To page
108
Abstract
This paper proposes two different types of benchmark models for the comparison of energy performance of water-cooled electric chillers: correlation-based models and Artificial Neural Network (ANN) models. Different techniques are proposed to establish the models and are evaluated with data collected from two chillers installed in an existing central cooling and heating plant. Both chillers have identical capacity and performance characteristics; however, they have quite different operating hours. The results show that models developed in this case study with 7 days of data monitored at the beginning of the summer season provide accurate results over the remaining of the summer and for the following summer. The proposed Multivariable Polynomial (MP) models for chillers provide the most accurate prediction with CV(RMSE) below 7% over the remaining of the summer season, and below 8% for the following summer season.
Keywords
Chiller , Ongoing commissioning , BENCHMARKING
Journal title
Applied Energy
Serial Year
2012