• Title of article

    Heat transfer analysis of short helical borehole heat exchangers

  • Author/Authors

    Zarrella، نويسنده , , Angelo and De Carli، نويسنده , , Michele، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2013
  • Pages
    15
  • From page
    1477
  • To page
    1491
  • Abstract
    In this paper a numerical model to analyze the thermal behaviour of vertical ground heat exchangers with a helical shaped pipe is presented. This type of configuration can be a suitable alternative to conventional ground heat exchangers, especially when the heating and cooling loads of the building are very low. del describes the heat transfer problem by means of a network of interconnected thermal resistances and capacitances. Moreover, as the investigated ground heat exchanger is usually installed in shallow depth, the model takes into account the interaction between the ground and the ambient environment which affects the fluid heat carrier temperature into the heat exchanger and, as a consequence, the energy efficiency of the heat pump. a sensitivity analysis on the mesh parameters, the presented model is compared with experimental data and the simulation results show good agreement with the measurements. Finally, analyses to investigate the influence of the weather conditions, of the axial heat transfer and of the pitch between the turns of the helical pipe for two types of ground are carried out.
  • Keywords
    Numerical simulation , heat transfer , Ground source heat pump systems , ground heat exchanger , borehole , Helical pipe
  • Journal title
    Applied Energy
  • Serial Year
    2013
  • Journal title
    Applied Energy
  • Record number

    1605986