Title of article :
Experimental study on the effects of the operation conditions on the performance of a chemisorption air conditioner powered by low grade heat
Author/Authors :
Kiplagat، نويسنده , , J.K. and Wang، نويسنده , , R.Z. and Oliveira، نويسنده , , R.G. and Li، نويسنده , , T.X. and Liang، نويسنده , , M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Abstract :
A chemisorption air conditioner with NaBr/expanded graphite composite sorbent and NH3 as refrigerant was designed and constructed to be powered by low temperature heat. The effect of independent variables (chilled water inlet temperature, heat source temperature and cycle time) on the coefficient of performance (COP) and cooling power of the machine was investigated with a 2k factorial design experimental set-up. This set-up was extended according to a central composite design to identify the coefficients of a 2° order polynomial equation that related the performance of the system and the independent variables. This equation was used to create response surfaces that enabled the identification of the operation conditions that maximized the machine performance. The experimental results indicated that the machine had a cooling power between 1.27 and 3.16 kW and a COP ranging from 0.28 to 0.48, depending on the operation conditions. The response surface analysis showed that when the heat sink was 25 ± 1 °C the maximization of the cooling power occurred at a driving heat source of at least 71 °C, in cycles not longer than 21 min. Contrarily, the maximization of the COP occurred at cycle time above 77 min, and heat source of around 56 °C. For simultaneous maximization of both the COP and the cooling power, the heat source should be 56 °C, and the cycle time between 20 and 25 min.
Keywords :
sodium bromide , Factorial design , Air conditioner , Chemisorption , Expanded graphite
Journal title :
Applied Energy
Journal title :
Applied Energy