Title of article
Model calibration for building energy efficiency simulation
Author/Authors
Mustafaraj، نويسنده , , Giorgio and Marini، نويسنده , , Dashamir and Costa، نويسنده , , Andrea and Keane، نويسنده , , Marcus، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2014
Pages
14
From page
72
To page
85
Abstract
This research work deals with an Environmental Research Institute (ERI) building where an underfloor heating system and natural ventilation are the main systems used to maintain comfort condition throughout 80% of the building areas. Firstly, this work involved developing a 3D model relating to building architecture, occupancy & HVAC operation. Secondly, the calibration methodology, which consists of two levels, was then applied in order to insure accuracy and reduce the likelihood of errors. To further improve the accuracy of calibration a historical weather data file related to year 2011, was created from the on-site local weather station of ERI building. After applying the second level of calibration process, the values of Mean bias Error (MBE) and Cumulative Variation of Root Mean Squared Error (CV(RMSE)) on hourly based analysis for heat pump electricity consumption varied within the following ranges: (MBE)hourly from −5.6% to 7.5% and CV(RMSE)hourly from 7.3% to 25.1%. Finally, the building was simulated with EnergyPlus to identify further possibilities of energy savings supplied by a water to water heat pump to underfloor heating system. It found that electricity consumption savings from the heat pump can vary between 20% and 27% on monthly bases.
Keywords
Heat pump water to water , Energy efficiency , Building energy simulation , Model calibration , Underfloor heating , Natural ventilation
Journal title
Applied Energy
Serial Year
2014
Journal title
Applied Energy
Record number
1608365
Link To Document