Title of article
Condensation of saturated vapours on compression and estimation of minimum suction superheating
Author/Authors
Felbab، نويسنده , , N.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
4
From page
527
To page
530
Abstract
A very simple criterion is derived to determine whether pure saturated vapours will be superheated or partially condensed when compressed, taking the isentropic efficiency of the compressor into account. The only fluid information that is required is the compressor suction (saturation) temperature, and the ideal gas heat capacity and enthalpy of vaporisation (latent heat) at that inlet temperature. In cases where partial condensation occurs, this approach allows for the estimation of minimum degrees of superheat required prior to compression to ensure that no liquid formation takes place. The approach relies on conditions where ideal gas behaviour can be assumed; as a rule of thumb, the method should not be applied at T/Tc > 0.6.
Keywords
Isentropic compression , Saturated vapour , Superheated , Condensation , Heat pump
Journal title
Applied Thermal Engineering
Serial Year
2013
Journal title
Applied Thermal Engineering
Record number
1905607
Link To Document