Title of article
Experimental study on evaporator performance in mobile air conditioning system using HFO-1234yf as working fluid
Author/Authors
Qi ، نويسنده , , Zhaogang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2013
Pages
7
From page
124
To page
130
Abstract
The widely used evaporators with two different type were experimentally studied in psychrometric calorimeter room using HFO-1234yf as working fluids. The evaporators types are laminated plate and microchannel parallel flow (PF) type. The experimental results compared with R134a system show that cooling capacity has different features in laminated plate evaporator and microchannel PF evaporator under different refrigerant pressure at expansion valve inlet. In general, cooling capacity of laminated plate evaporator of HFO-1234yf is reduced up to 8.0%. But in microchannel PF evaporator, cooling capacity is comparable and/or larger than that of R134a up to 6.5%. The HFO-1234yf evaporator air off temperature deviation is larger than that of R134a evaporator. The air side pressure drop is very close for both evaporators and refrigerants. HFO-1234yf refrigerant side pressure drop is larger than that of R134a for both evaporators.
Keywords
Parallel flow , HFO-1234yf , laminated plate , Evaporator , Microchannel
Journal title
Applied Thermal Engineering
Serial Year
2013
Journal title
Applied Thermal Engineering
Record number
1905640
Link To Document